Define how many info/data frames the device is allowed to send while holding the token.
Table 205: Range:
8-74 "I am" Service
Default value: [0] Send at power-up
Change during operation: True
Table 206: Option:
Select when the device should send the I am service message only at power-up.
Select when the device should send the I am service message continuously with an interval of approxi-
mately 1 minute.
8-75 Intialisation Password
Change during operation: True
Enter the password needed for execution of Drive Re-initialization from BACnet.
Table 207: Range:
8-79 Protocol Firmware version
Change during operation: False
Firmware revision of the drive is in index 0, Modbus is in index 1, Metasys N2 is in index 2, FLN is in index 3, BACnet is in index 4.
Table 208: Range:
4.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus communication via the FC port.
8-80 Bus Message Count
Change during operation: True
This parameter shows the number of valid telegrams detected on the bus.
Table 209: Range:
8-81 Bus Error Count
Change during operation: True
This parameter shows the number of telegrams with faults (for example, CRC fault), detected on the bus.
AU363928304090en-000101 / 130R0982 | 113Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide