13-00 SL Controller Mode
Default value: [0] Off
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
To enable the smart logic control to start when a start command is present, for example, via a digital input, Select [1] On. To disable
the smart logic control, select [0] Off.
Table 218: Option:
[0]
Off
Disable the smart logic controller.
[1]
On
Enable the smart logic controller.
13-01 Start Event
Default value: [39] Start command
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
To activate smart logic control, select the boolean (True or False) input.
Table 219: Option:
[0]
False
Enter the fixed value False in the logic rule.
[1]
True
Enter the fixed value True in the logic rule.
[2]
Running
The motor runs.
[3]
In range
The motor runs within programmed current ranges (parameter 4-50 Warning Current Low and pa-
rameter 4-51 Warning Current High).
[4]
On reference
The motor runs at reference speed.
[7]
Out of current range
The motor current is outside the range set in parameter 4-18 Current Limit.
[8]
Below I low
The motor current is lower than set in parameter 4-50 Warning Current Low.
[9]
Above I high
The motor current is higher than set in parameter 4-51 Warning Current High.
[16]
Thermal warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the drive, or
the thermistor.
[17]
Mains out of range
Mains phase loss warning or alarm, if parameter 14-12 Function at Mains Imbalance is not set at [2]
Disabled.
[18]
Reversing
The drive reverses.
[19]
Warning
A warning is present.
[20]
Alarm (trip)
An alarm is present.
[21]
Alarm (trip lock)
A trip lock alarm is present.
[22]
Comparator 0
Use the result of comparator 0 in the logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the logic rule.
AU363928304090en-000101 / 130R0982116 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals