13-00 SL Controller Mode
Change during operation: True
To enable the smart logic control to start when a start command is present, for example, via a digital input, Select [1] On. To disable
the smart logic control, select [0] Off.
Table 218: Option:
Disable the smart logic controller.
Enable the smart logic controller.
13-01 Start Event
Default value: [39] Start command
Change during operation: True
To activate smart logic control, select the boolean (True or False) input.
Table 219: Option:
Enter the fixed value False in the logic rule.
Enter the fixed value True in the logic rule.
The motor runs within programmed current ranges (parameter 4-50 Warning Current Low and pa-
rameter 4-51 Warning Current High).
The motor runs at reference speed.
The motor current is outside the range set in parameter 4-18 Current Limit.
The motor current is lower than set in parameter 4-50 Warning Current Low.
The motor current is higher than set in parameter 4-51 Warning Current High.
The thermal warning turns on when the temperature exceeds the limit in the motor, the drive, or
the thermistor.
Mains phase loss warning or alarm, if parameter 14-12 Function at Mains Imbalance is not set at [2]
Disabled.
A trip lock alarm is present.
Use the result of comparator 0 in the logic rule.
Use the result of comparator 1 in the logic rule.
Use the result of comparator 2 in the logic rule.
Use the result of comparator 3 in the logic rule.
Use the result of logic rule 0 in the logic rule.