Table 240: Option:
[0]
Trip
Trip the drive.
[1]
Warning
Issues a warning.
[2]
Disabled
No action.
[3]
Derate
The drive would derate.
14-15 Kin. Back-up Trip Recovery Level
Default value: 200.000 ReferenceFeedbackUnit
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: u_int32
Change during operation: True
Enter the kinetic back-up trip recovery level for the application. This recovery level is the minimum speed of the motor at which the
drive is to ramp up the speed.
Table 241: Range:
Min: 0
Max: 60000.000 ReferenceFeedbackUnit
Default value: 200.000 ReferenceFeedbackUnit
4.11.3 14-2* Reset Functions
Parameters for configuring auto reset handling, special trip handling and control card self-test or initialization.
14-20 Reset Mode
Default value: [0] Manual reset
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Define whether the drive waits for a manual reset, or resets itself automatically after tripping. In manual reset mode, press [RESET] or
use digital inputs to reset the drive.
N O T I C E
In automatic reset mode, the motor can start without a warning.
Table 242: Option:
[0]
Manual reset
Select [0] Manual reset to reset the drive via [Reset] or via the digital inputs.
[1]
Automatic reset x 1
Select [1]-[12] Automatic reset x 1… x20 to perform between 1 and 20 automatic resets after trip-
ping.
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
AU363928304090en-000101 / 130R0982132 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals