Select [13] Infinite Automatic Reset for continuous resetting after tripping.
14-21 Automatic Restart Time
Change during operation: True
To start the automatic reset function, enter the time interval from trip. This parameter is active when parameter 14-20 Reset Mode is
set to [1] - [13] Automatic reset.
N O T I C E
A value of 0 s cannot be set when parameter 14-20 Reset Mode is set to option [13] Infinite auto reset.
Table 243: Range:
14-22 Operation Mode
Default value: [0] Normal operation
Change during operation: True
To reset all parameter values to default, select [2] Initialisation.
Table 244: Option:
Select [0] Normal operation for normal operation of the drive with the motor in the selected application.
Select [2] Initialisation to reset all parameter values to default settings, excluding bus communication param-
eters, parameter group 15-0* Operating Data, and parameter group 15-3* Alarm Log. The drive is reset during
the next power-up. Parameter 14-22 Operation Mode also reverts to the default setting [0] Normal operation.
14-23 Typecode Setting
Change during operation: False
Service use only.
Table 245: Range:
14-27 Action At Inverter Fault
Default value: [1] Warning
Change during operation: True
Select how the drive acts in the case of overvoltage, overcurrent, short circuit, or grounding errors.
Table 246: Option:
Disable the protection filters and trip at the 1st fault.
Run the protection filters normally.