[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite auto reset
Select [13] Infinite Automatic Reset for continuous resetting after tripping.
14-21 Automatic Restart Time
Default value: 10 s
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
To start the automatic reset function, enter the time interval from trip. This parameter is active when parameter 14-20 Reset Mode is
set to [1] - [13] Automatic reset.
N O T I C E
A value of 0 s cannot be set when parameter 14-20 Reset Mode is set to option [13] Infinite auto reset.
Table 243: Range:
Min: 0 s
Max: 600 s
Default value: 10 s
14-22 Operation Mode
Default value: [0] Normal operation
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
To reset all parameter values to default, select [2] Initialisation.
Table 244: Option:
[0]
Normal op-
eration
Select [0] Normal operation for normal operation of the drive with the motor in the selected application.
[2]
Initialisation
Select [2] Initialisation to reset all parameter values to default settings, excluding bus communication param-
eters, parameter group 15-0* Operating Data, and parameter group 15-3* Alarm Log. The drive is reset during
the next power-up. Parameter 14-22 Operation Mode also reverts to the default setting [0] Normal operation.
14-23 Typecode Setting
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int8
Change during operation: False
Service use only.
Table 245: Range:
Min: 0
Max: 255
Default value: 0
14-27 Action At Inverter Fault
Default value: [1] Warning
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select how the drive acts in the case of overvoltage, overcurrent, short circuit, or grounding errors.
Table 246: Option:
[0]
Trip
Disable the protection filters and trip at the 1st fault.
[1]
Warning
Run the protection filters normally.
AU363928304090en-000101 / 130R0982 | 133Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals