14-28 Production Settings
Default value: [0] No action
Change during operation: False
Service use only.
Table 247: Option:
14-29 Service Code
Change during operation: True
Service use only.
Table 248: Range:
4.11.4 14-3* Current Limit Ctrl.
Parameters for configuring the current limit controller, which is activated when the motor current exceeds the preset current limits
(see parameter 4-18 Current Limit). These parameters are used to reduce torque as quickly as possible without losing control of the
motor.
14-30 Current Lim Ctrl, Proportional Gain
Change during operation: True
Enter the proportional gain value for the current limit controller. A higher value makes the controller react faster. Excessive value
setting leads to controller instability.
Table 249: Range:
14-31 Current Lim Ctrl, Integration Time
Change during operation: True
Control the current limit control integration time. Setting it to a lower value makes it react faster. A setting too low leads to control
instability.
Table 250: Range:
14-32 Current Lim Ctrl, Filter Time
Change during operation: True
AU363928304090en-000101 / 130R0982134 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide