Set a time constant for the current limit controller low-pass filter. A shorter period makes the control react faster to changes in cur-
rent.
Table 251: Range:
Min: 1 ms
Max: 100 ms
Default value: 26.0 ms
4.11.5 14-4* Energy Optimization
Parameters for adjusting the energy optimization level in both variable torque (VT) and automatic energy optimization (AEO) mode.
Automatic energy optimization is only active if parameter 1-03 Torque Characteristics is set to [3] Auto Energy Optim.
14-40 VT Level
Default value: 90%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: False
Enter the level of motor magnetization at low speed. Low values reduce energy loss in the motor, but also reduce load capability.
Table 252: Range:
Min: 40%
Max: 90%
Default value: 90%
14-41 AEO Minimum Magnetisation
Default value: 66%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: False
Enter the minimum allowable magnetization for AEO. Low values reduce energy loss in the motor, but also reduce resistance to
sudden load changes.
Table 253: Range:
Min: 40%
Max: 75%
Default value: 66%
14-44 d-axis current optimization for IPM
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: True
This parameter is available only when parameter 1-10 Motor Construction is set to [2] PM, salient IPM, non-Sat. Normally, VVC
+
PM
control automatically optimizes d-axis demagnetizing current based on d-axis and q-axis settings. When parameter 1-10 Motor Con-
struction is set to [2] PM, salient IPM, non-Sat, use this parameter to compensate the saturation effect at high load. Usually, decreas-
ing this value improves the efficiency. However, 0% means no optimization and the d-axis current is 0 (this is not recommended).
Table 254: Range:
Min: 0%
Max: 200%
Default value: 100%
4.11.6 14-5* Environment
These parameters help the drive to operate under special environmental conditions.
14-50 RFI Filter
Default value: [1] On
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
This parameter is only valid for drives of the following enclosure sizes:
IP20, 3x380–480 V, enclosure sizes H6–H8.
AU363928304090en-000101 / 130R0982 | 135Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals