16-11 Power [hp]
Default value: 0 hp
Parameter type: Range
2-setup: 1 setup
Conversion index: -3
Data type: u_int32
Change during operation: True
View the actual motor power in hp. The value shown is calculated based on the actual DC-link voltage and DC-link current.
Table 303: Range:
Min: 0 hp
Max: 1000 hp
Default value: 0 hp
16-12 Motor Voltage
Default value: 0 V
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
View the motor voltage, a calculated value used for controlling the motor.
Table 304: Range:
Min: 0 V
Max: 65535 V
Default value: 0 V
16-13 Frequency
Default value: 0 Hz
Parameter type: Range
2-setup: 1 setup
Conversion index: -1
Data type: u_int32
Change during operation: True
View the motor frequency, without resonance damping.
Table 305: Range:
Min: 0 Hz
Max: 6553.5 Hz
Default value: 0 Hz
16-14 Motor current
Default value: 0 A
Parameter type: Range
2-setup: 1 setup
Conversion index: -2
Data type: u_int16
Change during operation: True
View the motor current measured as an average value, I
RMS
.
Table 306: Range:
Min: 0 A
Max: 655.35 A
Default value: 0 A
N O T I C E
The maximum display value is 655.35 A, if the actual motor current surpasses 655.35 A, the data can be viewed from parameter
18-88 Motor current.
16-15 Frequency [%]
Default value: 0%
Parameter type: Range
2-setup: 1 setup
Conversion index: -1
Data type: u_int16
Change during operation: True
View the actual motor frequency as a percentage of parameter 4-14 Motor Speed High Limit.
Table 307: Range:
Min: 0%
Max: 6553.5%
Default value: 0%