Table 387: Option:
This function is not active.
The drive continues to run, but activates a warning (warning 93, dry pump). A drive digital output or a serial com-
munication bus can communicate the warning to other equipment.
The drive stops running and activates an alarm (alarm 93, dry pump). A drive digital output or a serial communi-
cation bus can communicate the alarm to other equipment.
N O T I C E
When this option is selected, do not set parameter 14-20 Reset Mode to [13] Infinite auto reset. Doing so
causes the drive to continuously cycle between running and stopping when a dry pump condition is de-
tected.
The drive stops running and activates an alarm (alarm 93, dry pump). A drive digital output or a serial communi-
cation bus can communicate the alarm to other equipment. If this option is selected and the dry pump condi-
tion is detected, the drive can only be reset manually.
22-27 Dry Pump Delay
Change during operation: True
Set delay before action set in parameter 22-26 Dry Pump Function takes place if a dry-pump condition is detected.
Table 388: Range:
4.16.3 22-3* No-flow Power Tuning
Parameters for setting up low power detection for the no flow function.
22-30 No-Flow Power
Change during operation: True
Readout of calculated no-flow power at actual speed.
Table 389: Range:
22-31 Power Correction Factor
Change during operation: True
Set a correction if no-flow detection reacts on a too low or too high power value.
Table 390: Range:
22-33 Low Speed [Hz]
Change during operation: True