Table 387: Option:
[0]
Off
This function is not active.
[1]
Warning
The drive continues to run, but activates a warning (warning 93, dry pump). A drive digital output or a serial com-
munication bus can communicate the warning to other equipment.
[2]
Alarm
The drive stops running and activates an alarm (alarm 93, dry pump). A drive digital output or a serial communi-
cation bus can communicate the alarm to other equipment.
N O T I C E
When this option is selected, do not set parameter 14-20 Reset Mode to [13] Infinite auto reset. Doing so
causes the drive to continuously cycle between running and stopping when a dry pump condition is de-
tected.
[3]
Man. Re-
set
Alarm
The drive stops running and activates an alarm (alarm 93, dry pump). A drive digital output or a serial communi-
cation bus can communicate the alarm to other equipment. If this option is selected and the dry pump condi-
tion is detected, the drive can only be reset manually.
22-27 Dry Pump Delay
Default value: 10 s
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
Set delay before action set in parameter 22-26 Dry Pump Function takes place if a dry-pump condition is detected.
Table 388: Range:
Min: 0 s
Max: 600 s
Default value: 10 s
4.16.3 22-3* No-flow Power Tuning
Parameters for setting up low power detection for the no flow function.
22-30 No-Flow Power
Default value: 0 kW
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int32
Change during operation: True
Readout of calculated no-flow power at actual speed.
Table 389: Range:
Min: 0 kW
Max: 1000 kW
Default value: 0 kW
22-31 Power Correction Factor
Default value: 100 %
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
Set a correction if no-flow detection reacts on a too low or too high power value.
Table 390: Range:
Min: 1 %
Max: 400 %
Default value: 100 %
22-33 Low Speed [Hz]
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
AU363928304090en-000101 / 130R0982168 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals