24-08 Mul FM Preset Reference
Change during operation: True
Enter the required multi preset reference/setpoint for firemode operation. For selecting dedicated references, select fire mode refer-
ence bit 0/1/2 [190], [191], or [192] for the corresponding digital inputs in parameter group 5-1* Digital Inputs.
Table 430: Range:
24-09 Fire Mode Alarm Handling
Default value: [1] Trip, crit. alarms
Change during operation: False
N O T I C E
Certain alarms can affect the lifetime of the drive. If 1 of these ignored alarms occurs while in fire mode, a log of the event is
stored in the fire mode log.
In fire mode log, the 10 latest events of alarms that affect warranty, fire mode activation, and fire mode deactivation are stored.
N O T I C E
The setting in parameter 14-20 Reset Mode is disregarded if fire mode is active (see parameter group 24-0* Fire Mode).
Table 431: Fire Mode Alarm Handling
Warranty affecting alarms
AU363928304090en-000101 / 130R0982 | 181Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide