Table 122: Range:
Min: -4999.000
Max: 4999.000
Default value: -4999.000
4-57 Warning Feedback High
Default value: 4999.000
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: int32
Change during operation: True
Use this parameter to set a higher limit for the feedback range. When the feedback exceeds this limit, the display reads Feedback
High. Warning bit 5 is set in parameter 16-94 Ext. Status Word. The output relay or digital output can be configured to indicate this
warning. The LCP warning indicator light is not turned on when this parameter set limit is reached.
Table 123: Range:
Min: -4999.000
Max: 4999.000
Default value: 4999.000
4-58 Missing Motor Phase Function
Default value: [1] Trip 10 s
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: False
Table 124: Option:
[0]
Off
No alarm is shown if a missing motor phase occurs.
[1]
Trip 10 s
The drive performs a scans for 10 s to detect a missing motor phase. When a missing motor phase is detected,
the drive trips.
4.6.4 4-6* Speed Bypass
Define the speed bypass areas for the ramps. 3 frequency ranges can be avoided.
4-61 Bypass Speed From [Hz]
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Enter the lower limits of the speeds to be avoided. Some systems call for avoiding certain output speeds due to resonance problems
in the system.
Table 125: Range:
Min: 0 Hz
Max: 500 Hz
Default value: 0 Hz
4-63 Bypass Speed To [Hz]
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Some systems call for avoiding certain output speeds due to resonance problems in the system. Enter the upper limits of the speeds
to be avoided.
Table 126: Range:
Min: 0 Hz
Max: 500 Hz
Default value: 0 Hz
4-64 Semi-Auto Bypass Set-up
Default value: [0] Off
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
AU363928304090en-000101 / 130R0982 | 67Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals