N O T I C E
If no run permissive signal is applied but either run, jog, or freeze commands is activated, the status
line in the display shows either Run Requested, Jog Requested, or Freeze Requested.
A signal applied puts the drive into hand-on mode as if [Hand On] is pressed and a normal stop com-
mand is overridden. If the signal is disconnected, the motor stops. To make any other start commands
valid, assign another digital input to Auto Start and apply a signal. The [Hand On] and [Auto On] keys
have no impact. The [Off] key overrides Hand Start and Auto Start. Press either [Hand On] or [Auto On]
to reactivate Hand Start and Auto Start. If there is no signal on Hand Start or Auto Start, the motor stops
regardless of any normal start command applied. If a signal is applied to both Hand Start and Auto
Start, the function is Auto Start.
A signal applied puts the drive into auto-on mode as if [Auto On] is pressed. See also [53] Hand Start.
Input for increment counting in the SLC counter.
Input for decrement counting in the SLC counter.
Input for reset of counter A.
Input for increment counting in the SLC counter.
Input for decrement counting in the SLC counter.
Input for reset of counter B.
A signal applied puts the drive into sleep mode.
A signal applied puts the lead pump into start mode.
A signal applied puts the lead pump into alternation mode.
A signal applied puts pump 1 into interlock mode.
A signal applied puts pump 2 into interlock mode.
A signal applied puts pump 3 into interlock mode.
A signal applied puts pump 4 into interlock mode.
A signal applied puts pump 5 into interlock mode.
Enable a selection of 1 of the 8 fire mode references according to Table 133.
Enable a selection of 1 of the 8 fire mode references according to Table 133.
Enable a selection of 1 of the 8 fire mode references according to Table 133.
AU363928304090en-000101 / 130R098274 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide