Table 164: Range:
Min: 0 mA
Max: 20 mA
Default value: 4 mA
6-23 Terminal 54 High Current
Default value: 20 mA
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Enter the high current value corresponding to the high reference/feedback set in parameter 6-25 Terminal 54 High Ref./Feedb. Value.
Table 165: Range:
Min: 0 mA
Max: 20 mA
Default value: 20 mA
6-24 Terminal 54 Low Ref./Feedb. Value
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: int32
Change during operation: True
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-20 Terminal 54 Low Voltage to
parameter 6-22 Terminal 54 Low Current.
Table 166: Range:
Min: -4999
Max: 4999
Default value: 0
6-25 Terminal 54 High Ref./Feedb. Value
Default value: Configuration dependent
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: int32
Change during operation: True
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-21 Terminal 53 High Voltage to
parameter 6-23 Terminal 53 High Current.
Table 167: Range:
Min: -4999
Max: 4999
Default value: Configuration dependent
6-26 Terminal 54 Filter Time Constant
Default value: 0.01 s
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Enter the time constant. This constant is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
54. A high time constant value improves dampening, but also increases the time delay through the filter.
Table 168: Range:
Min: 0.01 s
Max: 10 s
Default value: 0.01 s
6-29 Terminal 54 mode
Default value: [1] Voltage mode
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Select whether terminal 54 is used for current or voltage input.
AU363928304090en-000101 / 130R0982 | 95Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals