2.3.1 ADN-compliant Installation
To prevent spark formation in accordance with the
European Agreement concerning International Carriage of
Dangerous Goods by Inland Waterways (ADN), take
precautions for drives with protection rating of IP00
(Chassis), IP20 (Chassis), IP21 (Type 1), or IP54 (Type 12).
Do not install a mains switch.
Ensure that parameter 14-50 RFI Filter is set to
[1] On.
Remove all relay plugs marked RELAY. See
Illustration 2.1.
Check which relay options are installed, if any.
The only allowed relay option is VLT
®
Extended
Relay Card MCB 113.
1
2
e30bd832.10
1, 2 Relay plugs
Illustration 2.1 Location of Relay Plugs