5.1.9. Initialization to Default Settings
Initialize the adjustable frequency drive using default settings in two ways:
Recommended initialization (via par. 14-22)
1. Select par. 14-22
2. Press [OK]
3. Select “Initialization” ( for NLCP se-
lect “2” )
4. Press [OK]
5. Disconnect the power from the unit
and wait for the display to turn off.
6. Reconnecting the power resets the
adjustable frequency drive. Please
note that the first start-up takes a
few more seconds.
Par. 14-22 initializes everything except:
14-50
RFI 1
8-30
Protocol
8-31
Address
8-32
Baud Rate
8-35
Minimum Response Delay
8-36
Max Response Delay
8-37
Max Inter-char Delay
15-00 to 15-05 Operating data
15-20 to 15-22 Historical log
15-30 to 15-32 Fault log
NOTE
Parameters selected in
Personal Menu
, will stay present with the default factory
settings.
Manual initialization
NOTE
When carrying out manual initialization, serial communication, RFI filter settings
(par. 14-50) and fault log settings are reset.
Removes parameters selected in
Personal Menu
.
1. Disconnect from the power supply and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while powering up the
Graphical LCP (GLCP).
2b. Press [Menu] while the LCP 101, Numerical Display is powering up.
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed according to default settings.
This parameter initializes everything except:
15-00
Operating Hours
15-03
Power-ups
15-04
Overtemps
15-05
Overvolts
5. How to operate the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
62
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive and is the answer not in the manual?

Danfoss VLT HVAC Drive Specifications

General IconGeneral
TypeVLT HVAC Drive
STO (Safe Torque Off)Yes
EnclosureIP20
Output Frequency0-500 Hz
Brake ChopperBuilt-in (depending on frame size)
EMC FilterBuilt-in (depending on frame size)
CommunicationEthernet
Power Range0.37 kW to 630 kW
Input Voltage200-240V, 380-480V, 525-600V
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Ambient Temperature-10°C to +50°C (with derating above +40°C)
Storage Temperature-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Cooling MethodAir-cooled

Related product manuals