5.1.9. Initialization to Default Settings
Initialize the adjustable frequency drive using default settings in two ways:
Recommended initialization (via par. 14-22)
1. Select par. 14-22
2. Press [OK]
3. Select “Initialization” ( for NLCP se-
lect “2” )
4. Press [OK]
5. Disconnect the power from the unit
and wait for the display to turn off.
6. Reconnecting the power resets the
adjustable frequency drive. Please
note that the first start-up takes a
few more seconds.
Par. 14-22 initializes everything except:
14-50
RFI 1
8-30
Protocol
8-31
Address
8-32
Baud Rate
8-35
Minimum Response Delay
8-36
Max Response Delay
8-37
Max Inter-char Delay
15-00 to 15-05 Operating data
15-20 to 15-22 Historical log
15-30 to 15-32 Fault log
NOTE
Parameters selected in
Personal Menu
, will stay present with the default factory
settings.
Manual initialization
NOTE
When carrying out manual initialization, serial communication, RFI filter settings
(par. 14-50) and fault log settings are reset.
Removes parameters selected in
Personal Menu
.
1. Disconnect from the power supply and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while powering up the
Graphical LCP (GLCP).
2b. Press [Menu] while the LCP 101, Numerical Display is powering up.
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed according to default settings.
This parameter initializes everything except:
15-00
Operating Hours
15-03
Power-ups
15-04
Overtemps
15-05
Overvolts
5. How to operate the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
62
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
5