to move the cursor. A character can be changed when it is high-
lighted by a cursor. A character can be inserted by placing the
cursor between two characters and pressing or .
0-70 Set Date and Time
Value:
2000-01-01 00:00 –
2099-12-01 23:59
2000-01-01
00:00
Function:
Sets the date and time of the internal clock.
The format to be used is set in par. 0-71 and
0-72.
NOTE
This parameter does not display
the actual time. This can be read
in par. 0-89. The clock will not
begin counting until a setting
different from default has been
made.
0-71 Date Format
Value:
YYYY-MM-DD [0]
DD-MM-YYYY [1]
MM/DD/YYYY [2]
Function:
Sets the date format to be used in the LCP.
0-72 Time Format
Value:
24 H [*0]
12 H [1]
Function:
Sets the time format to be used in the LCP.
0-74 DST/Summertime
Value:
OFF [0]
Manual [2]
Function:
Choose how Daylight Saving Time/Summer-
time should be handled. For manual DST/
Summertime, enter the start date and end
date in par. 0-76 and 0-77.
0-76 DST/Summertime Start
Value:
2000-01-01 00:00 –
2099-12-31 23:59
2000-01-01
00:00
Function:
Sets the date and time when Summertime/
DST starts. The date is programmed in the
format selected in par. 0-71.
0-77 DST/Summertime End
Value:
2000-01-01 00:00 –
2099-12-31 23:59
2000-01-01
00:00
Function:
Sets the date and time when Summertime/
DST ends. The date is programmed in the for-
mat selected in par. 0-71.
1-00 Configuration Mode
Value:
Open-loop [0]
Closed-loop [3]
Function:
Open-loop
[0]: Motor speed is determined by
applying a speed reference, or by setting de-
sired speed when in Hand Mode.
Open-loop is also used if the adjustable fre-
quency drive is part of a closed-loop control
VLT
®
HVAC Drive Instruction Manual
6. How to program the adjustable frequency
drive
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
75
6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive and is the answer not in the manual?

Danfoss VLT HVAC Drive Specifications

General IconGeneral
TypeVLT HVAC Drive
STO (Safe Torque Off)Yes
EnclosureIP20
Output Frequency0-500 Hz
Brake ChopperBuilt-in (depending on frame size)
EMC FilterBuilt-in (depending on frame size)
CommunicationEthernet
Power Range0.37 kW to 630 kW
Input Voltage200-240V, 380-480V, 525-600V
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Ambient Temperature-10°C to +50°C (with derating above +40°C)
Storage Temperature-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Cooling MethodAir-cooled

Related product manuals