8-14 Configurable Control Word CTW
Option: Function:
Selection of control word bit 10 if it
is active low or active high.
[0] None
[1] * Profile default
[2] CTW Valid, active low
[3] Safe Option Reset
[4] PID error inverse
[5] PID reset I part
[6] PID enable
8-19 Product Code
Range: Function:
Size
related*
[0 -
2147483647 ]
Select [0] to readout the actual
fieldbus product code according
to the mounted fieldbus option.
Select [1] to readout the actual
Vendor ID.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communi-
cation port or fieldbus option.
[2] Logic
AND
Activates Start command via the fieldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTICE
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1]
PM non-salient SPM.
8-52 DC Brake Select
Option: Function:
[0] Digital
input
Activates Start command via a digital input.
8-53 Start Select
Option: Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
input
Activates start command via a digital input.
[1] Bus Activates start command via the serial communi-
cation port or fieldbus option.
[2] Logic
AND
Activates start command via the fieldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option: Function:
[0] Digital
input
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the fieldbus.
[1] Bus Activates the Reverse command via the serial
communication port or fieldbus option.
[2] Logic AND Activates the Reverse command via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR Activates the Reverse command via the fieldbus/
serial communication port OR via one of the
digital inputs.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port or fieldbus option.
[2] Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR Activate the set-up selection via the fieldbus/
serial communication port OR via one of the
digital inputs.
Parameters Operating Instructions
MG90U302 Danfoss A/S © Rev. 2014-02-27 All rights reserved. 45