EasyManuals Logo
Home>Danfoss>DC Drives>VLT PROFINET MCA 120

Danfoss VLT PROFINET MCA 120 User Manual

Danfoss VLT PROFINET MCA 120
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
8-13 Configurable Status Word STW
Option: Function:
[2] Alarm 68 Only Only set in case of an Alarm 68.
[3] Trip excl.
Alarm 68
Set in case of a trip, except if Alarm 68
executes the trip.
[10] T18 DI status. The bit indicates the status of terminal 18.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[11] T19 DI status. The bit indicates the status of terminal 19.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[12] T27 DI status. The bit indicates the status of terminal 27.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[13] T29 DI status. The bit indicates the status of terminal 29.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[14] T32 DI status. The bit indicates the status of terminal 32.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[15] T33 DI status. The bit indicates the status of terminal 33.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[16] T37 DI status The bit indicates the status of terminal 37.
”0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to protect
the frequency converter if there is a fault
on the brake modules. Use the output/
relay to cut out the main voltage from the
frequency converter.
[40] Out of ref.
range
[60] Comparator 0
See parameter group 13-1* Comparators. If
Comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61] Comparator 1
See parameter group 13-1* Comparators. If
Comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62] Comparator 2
See parameter group 13-1* Comparators. If
Comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63] Comparator 3
See parameter group 13-1* Comparators. If
Comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64] Comparator 4
See parameter group 13-1* Comparators. If
Comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65] Comparator 5
See parameter group 13-1* Comparators. If
Comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
8-13 Configurable Status Word STW
Option: Function:
[70] Logic Rule 0
See parameter group 13-4* Logic Rules. If
Logic Rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71] Logic Rule 1
See parameter group 13-4* Logic Rules. If
Logic Rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72] Logic Rule 2
See parameter group 13-4* Logic Rules. If
Logic Rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73] Logic Rule 3
See parameter group 13-4* Logic Rules. If
Logic Rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74] Logic Rule 4
See parameter group 13-4* Logic Rules. If
Logic Rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75] Logic Rule 5
See parameter group 13-4* Logic Rules. If
Logic Rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80] SL Digital
Output A
See 13-52 SL Controller Action. The output
goes high whenever the Smart Logic
Action [38] Set digital out A high is
executed. The output goes low whenever
the Smart Logic Action [32] Set digital out
A low is executed.
[81] SL Digital
Output B
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [39] Set digital out B high is
executed. The input goes low whenever
the Smart Logic Action [33] Set digital out B
low is executed.
[82] SL Digital
Output C
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [40] Set digital out C high is
executed. The input goes low whenever
the Smart Logic Action [34] Set digital out
C low is executed.
[83] SL Digital
Output D
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [41] Set digital out D high is
executed. The input goes low whenever
the Smart Logic Action [35] Set digital out
D low is executed.
[84] SL Digital
Output E
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [42] Set digital out E high is
executed. The input goes low whenever
the Smart Logic Action [36] Set digital out E
low is executed.
[85] SL Digital
Output F
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [43] Set digital out F high is
executed. The input goes low whenever
the Smart Logic Action [37] Set digital out F
low is executed.
Parameters Operating Instructions
44 Danfoss A/S © Rev. 2014-02-27 All rights reserved. MG90U302
88

Table of Contents

Other manuals for Danfoss VLT PROFINET MCA 120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT PROFINET MCA 120 and is the answer not in the manual?

Danfoss VLT PROFINET MCA 120 Specifications

General IconGeneral
BrandDanfoss
ModelVLT PROFINET MCA 120
CategoryDC Drives
LanguageEnglish

Related product manuals