Loading...
Application guidelines
79FRCC.PC.023.A7.22
Manifold compressors
Oil management concept
OS separator(CE)
Brand Chiyoda
Contact information
Email: sales@chiyodaseiki.com
Tel: +86(512)62833498
Address: No.1 Sheng gang Rd, Suzhou Industrial Park,
Jiang su, PRC, China.
Website: http://www.chiyodaseiki.com/
Model OS-165DFTDMCE
Outline
Type Centrifugal
ФD: Outter
Diameter(mm)
Φ165.2
Volume(L) 9.5
Inlet size(in 1" 3/8
outlet size (in) 1" 3/8
Footprint LxW(mm x
mm)
237.5x128
H1: Height(mm) 420
H2: Height(mm) 589
H: Height(mm) 612
Capillary tube
VZH088+SH120
mm*mm
VZH: ID Ø1.6*1400
SH: ID Ø1.4*1400
VZH117+SH140
mm*mm
VZH: ID Ø1.8*1500
SH: ID Ø1.4*1200
VZH117+SH184
mm*mm
VZH: ID Ø1.8*1500
SH: ID Ø1.6*1600
VZH170+SH180
mm*mm
VZH: ID Ø1.8*1380
SH: ID Ø1.6*1600
VZH170+SH295
mm*mm
VZH: ID Ø1.8*1380
SH: ID Ø1.8*1600
Strainer
Model:
Danfoss
(Orice
Φ2.0)(CE)
Mesh size 100
Solenoid
valve
Orice(mm) Φ2.0
Code number 032F1201
Connection(in) 1/4"
Solenoid
coil
24V
50Hz AC
Code
number
018F6257
Specication 1m 3-core cable
220-230V
50/60Hz
AC
Code
number
018F6282
Specication 1m 3-core cable