10
Protected 24 VAC Power Input – Fused metal oxide varistor (MOV) and transient voltage suppressor react to interrupt
the power from the circuit board if excessive amperage or over voltage condition is detected.
Isolation Transformer – Protection against ground loops, ground shorts, wiring errors and conducted electrical
interference.
Heavy Ground Planes and Power Foils – Large ground plane areas and wide power runs minimize disturbances
caused by EMI and other types of electrical interference.
Switching Power SupplyAllows for wide AC input voltage uctuation to reduce the effects of a power blackout while
still maintaining circuit board operation.
Fused RS-485 Network Lines on Network Communication Card – Disconnects the circuit board from the source of
current to protect the circuit board components.
Modulating Humidi er Control – Proportional control of steam generator humidi er provides additional re nements in
performance. (Optional Relay Module required.)
Humidi er Auto ush CycleAn adjustable ush cycle for infrared humidi ers to reduce deposit build-up. (Optional
Relay Module required.)
Three Additional Remote Alarms – Group or speci c alarm selection for remote alarm contact. (Optional Relay
Module required.)
Analog Inputs – Output values of four external analog sensors can be read on the processor display. (Optional Analog
board required.)
Under oor Water Detection Cable – Provides continuous water detection cable to encircle the entire unit.
Display Panel
CONDITIONS and DATA DISPLAYED
TEMPERATURE SETPOINT – ºF or ºC CURRENT TEMPERATURE – ºF or ºC
HUMIDITY SETPOINT – Percent of relative humidity CURRENT HUMIDITY – Percent of relative humidity
CURRENT DISCHARGE AIR or CHILLED WATER TEMPERATURE* - ºF or ºC
FUNCTIONS DISPLAYED
COOLING – 1
st
stage, 2
nd
stage, 3
rd
stage*, 4
th
stage* REHEAT – 1
st
stage, 2
nd
stage, 3
rd
stage, hot water*
CHILLED WATER FLOW – 10 to 100% (based on VDC output) ENERGY SAVER* - hours of operation
DEHUMIDIFICATION - hours of operation HUMIDIFICATION - hours of operation
* This optional feature or data display may require additional components and/or sensors.