32
MENU - To proceed to Group 4 - ALARMS
Display will read: GROUP 4 – ALARMS
SELECT - To view Group 4 - ALARMS
Display will read: 4-1 AUDIO ALARM MODE
SELECT or - To display current setting
Display will read: 4-1 AUDIO ALARM MODE
AUDIO ALARM: LONG BEEP
SELECT or - to scroll through the available selections.
The following can be viewed, audio alarm will also sound:
NONE
SHORT BEEP
LONG BEEP
FULL ON
Factory setting is: LONG BEEP
MENU - To view next sub-menu
Display will read: 4-2 CHANGE HI TEMPERATURE ALARM LIMIT
SELECT or - To view current setting
Display will read: 4-2 CHANGE HI TEMPERATURE ALARM LIMIT
SET AT: xxF (C)
SELECT or - To change current setting
(High temperature alarm can be adjusted from 70 to 90ºF (21 to 32ºC) in 1º increments. There is also a disable
function. When the disable function is set the display will read:
4-2 CHANGE HI TEMPERATURE ALARM LIMIT
DISABLE HI TEMPERATURE ALARM
Factory setting is: 80F (C)
MENU - To view next sub-menu
Display will read: 4-3 CHANGE LO TEMPERATURE ALARM LIMIT
SELECT or - To view current setting
Display will read: 4-3 CHANGE LO TEMPERATURE ALARM LIMIT
SET AT: xxF (C)
SELECT or - To change current setting
Low temperature alarm can be adjusted from 55 to 75ºF (12.8 to 23.9ºC) in 1º increments. There is also a
disable function.
When the disable function is set the display will read:
Group 4