SELECT or - To view current setting
Display will read 3-24 DIFFERENTIAL PRESSURE SETPOINT
SET AT: 0.00” H2O
Differential pressure setpoint is adjustable from 0.00 TO 1.00” H2O.
Factory setting is 0.00” H2O.
SELECT or - To change current setting.
MENU - To view Sub-Menu 3-25: DIFFERENTIAL PRESSURE DEADBAND
Display will read 3-25 DIFFERENTIAL PRESSURE DEADBAND
SELECT or - To view current setting.
Display will read 3-25 DIFFERENTIAL PRESSURE DEADBAND
SET AT: 0.00” H2O
Differential pressure setpoint is adjustable from 0.05 to 0.10” H2O.
Factory setting is 0.05” H2O.
MENU - To view Sub-Menu 3-26: FAN SPEED RESPONSE RATE
Display will read 3-26 FAN SPEED RESPONSE RATE
SELECT or - To view current setting
Display will read 3-26 FAN SPEED RESPONSE RATE
RESPONSE TIME: 05 SECONDS
Fan speed response time is adjustable from 6 to 60 seconds.
Factory setting is 5 seconds.
SELECT or - To change current setting.
or
EXIT - Press EXIT to return to Group 3 - OPERATION
EXIT - Press EXIT again to return to Current Operating Functions & Status Display