Supplemental Compressor Operation during Energy Save Mode – Extends the savings from Energy Saver by
allowing one or two compressors to supplement cooling as needed when Energy Saver cooling is not suf cient.
Temperature Anticipation – Responds to varying rates of temperature change.
Humidity Anticipation – Modi es the humidity setpoint to diminish excess humidi cation and dehumidi cation.
Dehumidi cation Mode Lockout – Inhibits dehumidi cation if not required for system performance.
Start Time Delay – Programmable time delay staggers the start-up of multiple units to prevent high power demand
peaks.
Chilled Water, Energy Saver and Hot Water Coil Flush Cycle – Periodically circulates uid in the coil to reduce
deposit buildup in system.
Automatic Compressor Rotation – Periodically rotates the lead/lag sequence to balance compressor run times.
Automatic Reheat Element Rotation – Rotates the staging sequence to balance the run times of the heating elements.
Energy Saver (Glycol) or Auxiliary Chilled Water Operation – Two types of Energy Saver Systems are available.
Programmable Water Under Floor Alarm - Can shut down unit or just compressors.
DIAGNOSTIC AND SERVICE FEATURES
Alarms Displayed in Order of Occurence – Sequence with time of occurrence assist in diagnosing the cause of
alarms.
Programmable Delays for Optional Alarms – Reduces nuisance and false alarms caused by temporary or transient
conditions.
Manual Diagnostic Program – Provides accessible procedures to test the processor and major system components.
Manual Override for Blower, Cool 1 and 2, Heat 1, Humidi cation and Water Valve – The control circuit is operable
even if the processor is not functioning properly.
Adjustable Alarm Limits – Threshold levels for temperature and humidity alarms are programmable.
Four Programmable Optional Alarms – In addition to the standard alarms, four additional alarms are programmable.
Select Alarms Optionally Disabled – Nonessential alarms can be turned off.
Audio Alarm Tone – Four programmable alarm tones.
PROTECTIVE AND SAFETY FEATURES
Metal Shell Enclosure with Sealed Front Control Panel – Provides electromagnetic interference (EMI) protection and
general protection against environmental contamination and handling damage.
Watch Dog TimerAutomatically resets the circuit board, clears any corrupted memory and restarts the system with
minimal interruption in case of an un ltered transient signal.
Opto-Signal Inputs – Isolates the circuit board from electrical noise or static from contactors, compressors and motors
that can contaminate the power at the circuit board.

Other manuals for Data Aire DAP III