22
SELECT or - To display humidity deadband.
Display will read: 2-4 CHANGE HUMIDITY DEADBAND
SET AT: nn.n%
SELECT or - Scroll to desired setting, in 0.1% increments.
(Humidity deadband is adjustable from 1.0 – 15.0% relative humidity. Factory setting is 3.0%.)
MENU - To display SUB-MENU 2-5: CHANGE COOLING STAGE-TO-STAGE DB
Display will read: 2-5 CHANGE COOLING STAGE-TO-STAGE DB
SELECT or - To view cooling stage-to-stage deadband.
Display will read: 2-5 CHANGE COOLING STAGE-TO-STAGE DB
SET AT: n.nF
SELECT or - Scroll to desired setting, in 0.1º increments.
(Cooling stage-to-stage deadband is adjustable from 0.3 to 3.0ºF / -17.6 to -16.1ºC. Factory setting is 0.3º F/C.)
MENU - To display SUB-MENU 2-6:CHANGE E-SAVER CW TEMPERATURE SETPOINT
Display will read: 2-6 – CHANGE E-SAVER CW TEMPERATURE SP
SELECT or - To view current E-SAVER CW temperature setpoint.
Display will read: 2-6 – CHANGE E-SAVER CW TEMPERATURE SP
ENERGY SAVER AVAILABLE AT nn
F
SELECT or - Scroll to desired setting, in 1º increments.
(Energy Saver CW temperature setpoint is adjustable from 40 to 60ºF / 4.4 to 15.6ºC Factory setting is 50ºF/C)
MENU - To display SUB-MENU 2-7: CHANGE E-SAVER CW TEMPERATURE DEADBAND
Display will read: 2-7 – CHANGE E-SAVER CW TEMPERATURE DB
SELECT or - To view E-SAVER CW temperature deadband.
Display will read: 2-7 – CHANGE E-SAVER CW TEMPERATURE DB
SET AT n.nF
SELECT or - To scroll to desired setting, in 1º increments.
(Energy Saver CW temperature deadband is adjustable 1.0 to 5.0ºF/ -17.2 to -15ºC. Factory setting is 1.0ºF/C)
EXIT - Press EXIT to return to GROUP 2 - Setpoints
EXIT - Press EXIT again to return to operational mode.
OR