54
SELECT - To view current setting
Display will read: 8-5 – SET-BACK REHEAT
SETBACK HEAT: nnF (C)
SELECT or - To change setting. The range is from 1 – 30 in 1
O
increments.
MENU - To view next sub-menu
Display will read: 8-6 SET-UP DEHUMIDIFICATION
SELECT - To view current setting
Display will read: 8-6 SET-UP DEHUMIDIFICATION
SETUP DEHUMIDIFICATION: nn%
SELECT or -
To change setting. The range is from 1 – 30% in 1% increments.
MENU - To view next sub-menu
Display will read: 8-7 SET-BACK HUMIDIFICATION
SELECT - To view current setting
Display will read: 8-7 SET-BACK HUMIDIFICATION
SET BACK HUMIDIFICATION: nn%
SELECT or - To change setting. The range is from 1 – 30% in 1% increments.
MENU - To view next sub-menu
Display will read: 8-8 MONDAY SCHEDULE
SELECT or - To view current setting
Display will read: 8-8 MONDAY SCHEDULE
SCHEDULE TYPE: aaaaaaaa/aa
SELECT or - To change setting. There are two settings: ON/OFF and SETBACK/UP
In the ON/OFF mode the unit will operate during the occupied time with standard settings and turn OFF (shut off) during the
unoccupied time. In the SETBACK/UP mode the unit will operate with standard set points during occupied time and operated
with modifi ed set points (standard set points plus set-backs programmed in menus 8-4 through 8-7) during unoccupied times.
Menus 8-8 through 8-14 permit you to select the mode, the hour to begin and end occupancy or N/C - no change. This permits
a more energy effi cient operation of the unit.
MENU - To view next menu
Display will read: 8-8 MONDAY SCHEDULE
OCCUPIED hh:mm
SELECT or - To change setting. Time can be set from 00:00 hours to 23:45 hours in 15
minute increments. N/C (no change) is also an option.
MENU - To view next menu
Display will read: 8-8 MONDAY SCHEDULE
UNOCCUPIED hh:mm
Allows one to decrease reheat set
point in Day Schedule.
Allows one to increase
dehumidifi cation set point in Day
Schedule.
Allows one to decrease
humidifi cation set point in Day
Schedule.