Problem Possible Cause Check or Remedy
Humidi cation does not
come on - continued
Loose connection on plugs on cable
P6-5
F2 RELAY fuse of DAP III is blown
Panel is operating in manual override
and the humidi er override is not ON
Faulty humidi er relay
Incorrect con guration
Humidi er problem alarm
Restricted by interstage time delay or
auto ush timer panel
Check connections use humidi er manual
override switch to test
Replace with 8 amp fuse
Check manual override switches
Use manual Test Relay tests sub menu 9-3 to
check.
Check settings in sub menu 5-6.
Correct the alarm.
Wait 5-10 minutes or reset the panel. Refer to
humidi cation logic
Modulating humidi er does
not come on
No call for humidi cation
Loose connection on plugs or cable
P15-16, P15-17
No DC output to humidi er controller
Incorrect settings
Check humidity setpoint and deadband
Check connections. Use humidi er manual
override switch to test.
Use manual diagnostic output test sub menu
9-4
Check settings in sub menu 5-6
Optional auto ush timer
does not work
Incorrect setting
Loose connection on Relay module
Auto ush timer of OFF
Loose connections on cable
Faulty auto ush relay
Check setting in sub menu 5-10
Check Relay Module connections on PC
board, check pin P15-4
Check setting in sub menu 5-10
Check connections. Refer to wiring diagram
Use manual Test Relay sub menu 9-3 to
check.
Dehumidi cation does not
come on
No call for dehumidi cation
Inhibited by no air ow
Incorrect con guration
Inhibited by humidity anticipation
Inhibited by reheat
Check humidity setpoint and deadband
Correct no air ow alarm
Check settings in sub menus 3-9 and 3-15.
Refer to humidity logic. Check sub menu 3-15
Refer to dehumidi cation logic. Check sub
menu 3-9