53
R407C) required by the order. Please see the Air-Cooled Condenser User Manual for more
detailed information on fan speed control.
Pre-Charge Fixed Speed Compressor
1. After the system has been properly evacuated. Calculate the proper charge for each
circuit by following the steps and the data in the tables below.
2. Select the model and refrigerant charge for evaporator section and condenser in
accordance with Table 2 gForce GF Dual Circuit Units.