MAINTENANCE/INSPECTION CHECKLIST
(NOTE: Maintenance/inspection items are monthly unless otherwise specified.)
Reheat
Inspect element (and clean if required)
Check wiring
Record amps A
Refrigeration Piping
Check for lines (leaks/lines secure)
Check capillary lines
Condensate Pan and Pump (if equipped)
Check for leaks
Check for debris
Inspect/check float operation
Check pump operation
Condensers (Water-Cooled)
Check for leaks
Entering/leaving water temperatures: Entering T °F Leaving T °F
Compressor (Monthly)
Check for oil leaks
Check compressor mounting
Inspect wire connection
Compressor (Quarterly) Compressor 1 Compressor 2
Record suction pressure
PSIG
PSIG
Record discharge pressure
PSIG
PSIG
Record superheat °F °F
Record sub-cooling °F °F
Check high pressure cut-out PSIG PSIG
Check low pressure cut-in PSIG PSIG
Check low pressure cut-out PSIG
Record compressor amp draw L1 A L1 A
L2 A L2 A
L3 A L3 A