EasyManua.ls Logo

Datakom D-300 MK2 - Page 83

Datakom D-300 MK2
139 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-300 MK2 User Manual Firmware V-6.3
L052D01-EN - 83 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Current
Unbalance Limit
%
0
100
0.0
If any genset phase current differs from
the average more than this limit, it will
generate a Current Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
Genset Current
Unbalance Action
-
0
3
0
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
Genset Reverse Power
Warning Limit
kW
0
50000
0
If the genset power is negative and
goes above this limit then a REVERSE
POWER warning will be generated. If
this parameter is set to 0 then reverse
power fault is not monitored.
Genset Reverse Power
Loaddump Limit
kW
0
50000
0
If the genset power is negative and
goes above this limit then a REVERSE
POWER loaddump will be generated.
Genset Reverse Power
Fail Timer
sec
0
120
5
If the genset power is negative and over
limits during this timer, a reverse power
fault will occur.
Genset Overcurrent Limit
Amp
0
50000
0
If one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
Genset Overcurrent
Limit-2
Amp
0
50000
0
When secondary voltage is selected, if
one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
Genset Overcurrent
Limit-3
Amp
0
50000
0
When tertiary voltage is selected, if one
of the genset phase currents goes over
this limit when feeding the load, this will
generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
Genset Overcurrent
Action
-
0
3
0
0: shutdown alarm
1: loaddump alarm
Overcurrent Time
Multiplier
0
1
64
16
This parameter defines the reaction
speed of the overcurrent detector. A
higher number means higher sensitivity.
Detailed explanation is given at chapter:
“Overcurrent Protection”
16.2. ELECTRICAL PARAMETERS GROUP (continued)

Table of Contents

Related product manuals