DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 53
Engine settings – Crank disconnect Value
Crank disconnect on generator frequency 21.0Hz
Crank disconnect oil pressure <Disabled>
Check oil pressure prior to starting Yes
Engine settings – speed Value
Underspeed trip
#
1250 RPM Disabled
Underspeed prealarm
#
1350 RPM Disabled
Overspeed prealarm
#
1650 RPM Disabled
Overspeed trip
#
1750 RPM Disabled
Overspeed overshoot
#
0% Disabled
Plant battery settings Trip Return
Under volts warning
#
8.0V DC 9.0V DC
Over volts warning
#
33.0V DC 32.0V DC
Charge alternator warning
#
6.0V DC N/A
Exercise scheduler settings Value
Enable exercise scheduler No
Comms Value
Site identity
Genset ID
Modem mode No modem
Modem init (not auto answer) E0S7=60S0=0&S0&C1&D3
Modem init (auto answer) E0S7=60S0=2&S0&C1&D3
Modem Hang H0
Master inactivity timeout 5s
Slave ID 10 (Default)
Baud Rate 19200 (Default)
Languages Value
Fixed Languages
#
English (UK)
User configured languages Not used