DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
52 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
Timer settings Value
Mains transient delay
#
2s
Start delay
#
5s
Pre-heat
#
0s
Cranking time
#
10s
Crank rest time
#
10s
Smoke limit 0s
Smoke limit off 0s
Safety on delay
#
10s
Overspeed overshoot
#
2s
Warming up time
#
0s
Transfer time
#
0.7s
Breaker close pulse 0.5s
Breaker trip pulse 0.5s
Return delay
#
30s
Cooling time
#
1m
ETS solenoid hold 0s
Fail to stop delay
#
30s
Generator transient delay
#
1s
Battery low volts delay
#
1m
Battery high volts delay
#
1m
LCD page timer 5m
Mains (utility) settings – Voltage/frequency Trip Return
Under volts trip
#
184V AC 207V AC
Over volts trip
#
276V AC 253V AC
Under frequency trip
#
45.0 Hz 48.0 Hz
Over frequency trip
#
55.0 Hz 52.0 Hz
Generator settings – Voltage/frequency Trip Return
Under volts trip
#
184V AC N/A
Under volts pre-alarm
#
196V AC 207V AC
Over volts pre-alarm
#
265V AC 253V AC
Over volts trip
#
276V AC N/A
Under frequency trip
#
40.0 Hz N/A
Under frequency pre-alarm
#
42.0 Hz 45.0 Hz
Over frequency pre-alarm
#
55.0 Hz 52.0 Hz
Over frequency trip
#
57.0 Hz N/A
Droop
#
Disabled N/A
Droop %
#
0.0% N/A
Loading Voltage 207V Ph-N
Loading Frequency 45 Hz
Alternative Voltage
#
230v norm / 115v alt Disabled on module
Alternative frequency
#
50Hz norm / 60Hz alt Disabled on module
Generator settings – Current/power Value
Generator CT primary 600A
Generator CT secondary 5A
CT location Generator Only
Generator full load rating
#
500A
Delayed High Current
#
100% ( 500A )
Trip Curve 36