Output, Command Engine
Description Notes
Activate Warm Up Ramp Activate warm up ramp
Battery test Activate battery test
Eng. heater manual ctrl. Enable/disable the engine heater function.
Auto start/stop ON = Start, OFF = Stop.
Remote start Pulse signal.
Remote stop Pulse signal.
Start and close GB Start engine and close generator breaker.
GB open and stop Open generator breaker and stop engine.
Output, Command Breakers
Description
Notes
GB close inhibit Prevents the generator breaker from closing.
Open GB Open the generator breaker.
Close GB Close the generator breaker.
Open MB Open the mains breaker.
Close MB Close the mains breaker.
MB close inhibit Prevents mains breaker from closing.
Output, Command Plant
Description
Notes
Select application [1-4]
Power management: Select the power management application from the
controller.
Output, Command Power management
Description
Notes
Set to local start Select local start in a power management application.
Set to remote start Select remote start in a power management application.
Update mode local
The running mode for the local controller in the power management system is
updated to the selected mode.
Update mode on all
The running mode for all controllers in the power management system is updated
to the selected mode.
Store common settings See Handling settings for sections in Option G5.
Abs. prio. handling Absolute (fixed) start priority.
Rel. prio. handling Relative (running timer based) start priority.
Activate base load Activates the base load function.
Deactivate base load Disables the base load function.
Activate N+X extra DGs
Start and connect extra gensets based on the largest running genset (secured
mode). See Option G5 for more information.
Deactivate N+X extra DGs N+X mode is deactivated.
First priority Forces this controller to have the first priority in a power management system.
Use Ana LS instead of CAN Forces the power management system to use the analogue load share line.