5.4 Status texts
Status text Condition
ACCESS LOCK The configurable input is activated, and the operator tries to activate one of the blocked keys.
ADAPT IN PROGRESS The controller is receiving the application that it has just connected to.
ADD ESS TO CAN PMS? Easy connect: Add ESS to PMS plant.
AMF ACTIVE The controller is in auto mode during a mains failure.
AMF AUTO The controller is in auto mode and ready to respond.
AMF SEMI The controller is in semi-auto mode and waiting for operator input.
Aux. test ##.#V ####s The controller power supply test is activated.
AUX TEST ST. SEQ. Genset battery test.
AUX TEST START SEQ. Genset battery test.
AWAITING ESS RUN OK The ESS must be operating before attempting to close the breaker.
AWAITING MODE INFO
The selected mode is not supported by the configured application. Select another application
mode.
BATTERY BOOST ACTIVE The battery is boosting the DC voltage to increase the state of charge (SOC).
BB BLOCKED BY GB Power management: GB has a position failure.
BB BLOCKED BY MB Power management: MB has a position failure.
BB BLOCKED BY TB Power management: TB has a position failure.
BB V/Hz OK IN The voltage and frequency will be okay in ###s.
BB VOLTAGE DETECTED Voltage detected on the busbar.
BESS INITIALIZING The controller is establishing communication to the BESS.
BLACKOUT ENABLE Blackout close when there is a CAN failure.
BLOCKED FOR CLOSING The breaker is unable to close.
BLOCKED FOR START There are active alarms.
BROADCAST ABORTED Power management: Broadcast terminated.
BROADCAST COMPLETED Power management: Successful broadcast of application.
BROADCASTING APPL.
Power management: Broadcast one of the four applications from one controller to the other
controllers in the power management system, through the CAN line.
CHECKING CAN PMS Easy connect: Checking for other units on the PMS CAN line.
CLOSE DELAY ES breaker close delay.
COMPENSATION FREQ. Compensation is active. The frequency is not at the nominal setting.
DELAY REG. Regulation is delayed until after start.
DELOAD The controller is decreasing the load of the genset in order to open the breaker.
DELOAD ERROR There is an error when deloading.