Level 2 Range
Over-current Threshold
(OVER CURR THRESHOLD)
5 to 10000 A
Over-current Delay
(OVER CURR DELAY)
1 to 600 s
CT Correction Factor 0.900 to 1.100
CT Location
(CT LOCATION)
On Alt Output Cable
On Load Cable
Table 6.25 Earth Leakage/Fan Current Monitoring (EARTH CURR MON)
Level 2 Range
Current Monitoring
(FAN / EARTH MOMN)
Earth Leakage Current
Fan Current
Current CT Ratio
(CT RATIO)
0 to 8000 / 5
High Current Action
(HIGH CURR ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
High Current Threshold
(HIGH CURR THRESH)
0.1 to 10.0 A
Current Delay
(CURR DELAY)
5 to 60 s
Low Current Action
(LOW CURR ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Low Current Threshold
(LOW CURR THRESH)
0.1 to 9.9 A
Table 6.26 Load Monitoring (LOAD MONITOR)
Level 2 Range
Generator Rating
(GEN RATING)
0 to 8000 kW
Overload Action
(OVERLOAD ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Overload Threshold
(OVERLOAD THRESHOLD)
50 to 150 %
Overload Monitoring Delay
(OVERLOAD MON DELAY)
1 to 600 s
Unbalanced Load Action
(UNBAL LOAD ACTION)
None
Warning
Electrical Trip
Shutdown
USER MANUAL 4189341227A UK Page 35 of 86