Level 2 Range
Action
None
Notification
Warning
Electrical Trip
Shutdown
Activation
Never
From Enigine Start
From Monitoring On
Always
Activation Delay 0 to 60 s
Table 6.36 Lube Oil Pressure (LOP)
Level 2 Range
Low Level Shutdown
Enable
Disable
Shutdown Threshold 0.0 to 9.8 Bar
Low Level Warning
Enable
Disable
Warning Threshold 0.2 to 10.0 Bar
Table 6.37 Engine Coolant Temperature (ENG COOL TEMP)
Level 2 Range
High Level Shutdown
Enable
Disable
Shutdown Threshold 27 to 300 °C
High Level Warning
Enable
Disable
Warning Threshold 25 to 298 °C
6.2.10 Maintenance
Table 6.38
Maintenance (MAINT ALARM)
Level 2 Range
Alarm Action
(ACTION)
Notification
Warning
Due At Engine Hours
(DUE AT ENGINE HOURS)
10 to 65000 hours
Alarm Due Date
(ALARM DUE DATE)
dd/mm/yyyy
6.2.11 Password ID
Table 6.39
ID
Level 1 Level 2 Range
(ENG SR NO) ############ Numbers: 0 to 9
USER MANUAL 4189341227A UK Page 40 of 86