Level 1 Level 2 Range
Letters: A to Z
(PASSWORD 1) #### Numbers: 0 to 9
(PASSWORD 2) #### Numbers: 0 to 9
6.2.12 Rotary actuator (SGC 421 only)
Table 6.40
General (GENERAL)
Level 2 Range
Actuator Application
(ACTUATOR APPLN)
As E-Governor
As Start/Stop Device
Actuator Speed
(ACTUATOR SPEED)
1 to 10 x 25 Hz
Actuator Direction
(ACTUATOR DIRECTION)
Clockwise to Stop
Anti clockwise to stop
Governing Mode
(GOVERNING MODE)
Fixed Speed
Table 6.41 Engine Start Strategy (ENG START STRGY)
Level 2 Range
Cranking Steps
(CRANKING STEPS)
50 to 5000
Initial Low Speed Delay
(INIT LOW SPEED DELAY)
0 to 180 s
Initial Low Speed
(INIT LOW SPEED)
500 to 1800 RPM
PID Trigger Speed
(PID TRIGGER SPEED)
20 to 2800 RPM
Ramp Up Time
(RAMP UP TIME)
1 to 180 s
PID On Time
(PID ON TIME)
1 to 180 s
Table 6.42 Generator EGov Config (GEN EGOV CNFG)
Level 2 Range
Set Speed Selection
(SET SPEED SELECTION)
Fixed (0 % Droop)
Speed Bias Input (0-5 V)
Load Based Droop
(LBD) Droop
(DROOP)
0 to 4 %
Target Speed
(TARGET SPEED)
500 to 4000 RPM
Proportional Gain (Kp)
(PROPORTIONAL GAIN)
0 to 1000
Integral Gain (Ki)
(INTEGRAL GAIN)
0 to 2000
USER MANUAL 4189341227A UK Page 41 of 86