Level 2 Range
(OF ENABLE) Disable
(OF) Return
(OF RETURN)
25.0 to 74.0 Hz
(OF) Trip
(OF TRIP)
26.0 to 75.0 Hz
6.2.9 Engine
Table 6.30
Crank Disconnect (CRANK DISCONN)
Level 2 Range
Start Attempts
(START ATTEMPTS)
1 to 9
Disconnect on Oil Pressure Sensor
(DISCONN ON LOP SENS)
Enable
Disable
Monitor Pressure Sensor Before Crank
(MON LLOP BEF CRANK)
Enable
Disable
Pressure Sensor Monitoring Threshold
(DISCONN LOP SENS)
0.5 to 10.0 bar
Monitor Pressure Switch Before Crank
(MON LOP BEF CRANK)
Enable
Disable
Disconnect on Oil Pressure Switch
(DISCONN ON LLOP SW)
Enable
Disable
Pressure Switch Transient Time
(LLOP SW TRANS TIME)
0.0 to 3.0 s
Crank Disconnect At Alt Frequency
(ALT FREQUENCY)
10 to 70 Hz
Crank Disconnect At Engine Speed
(ENGINE SPEED)
150 to 4000 RPM
Disconnect On Charging Alt Voltage
(DISC ON CHG ALT VOLT)
Enable
Disable
Charging Alt Disconnect Volt Threshold
(CHG ALT THRESHOLD)
5.0 to 30.0 V
Table 6.31 Speed Monitoring (SPEED MONITOR)
Level 2 Range
Engine Speed Sense Source
(SPEED SENSE SOURCE)
Alternator frequency
Magnetic Pickup
W-Point Frequency
Flywheel Teeth (Magnetic Pickup) 1 to 300
W-Point Frequency@ 1500 0 to 500
Under-speed Shutdown
(UNDER SPEED SHUTDOWN)
Enable
Disable
Under-speed Threshold
(UNDER SPEED THRESH)
0 to 3600 RPM
Under-speed Delay
(UNDER SPEED DELAY)
1 to 60 s
USER MANUAL 4189341227A UK Page 37 of 86