13.5 Engine communication settings
Use the DEIF Smart Connect software to configure engine communication in the SGC controller.
Open DEIF Smart Connect and connect to the SGC controller, then select Start > Engine > Engine Control unit (ECU) for the
engine communication settings window.
No. Function
1 Select the engine type from the drop-down list.
2 Select types of measurements from the engine/ECU.
3 Configure the settings for the ECU communication failure alarm.
4
Configure the settings for the diagnostic lamps on the ECU
Amber lamp
Red lamp
Malfunction lamp
Protect lamp
See the specific documentation for the engine/ECU for more information.
5
Select the actions that SGC controls for the engine/ECU
Engine speed
Engine start/stop
Engine preheat
6
Configure source addresses for the SGC controller and the engine/ECU.
See the specific documentation for the engine/ECU for information about the source address.