Start the engine
Shutdown Alarm
Warning Alarm
Notification
Press the Stop/Config button.
Press the Start
button to crank the engine
If the Start button is pressed in this mode, the
controller sends a Start command and the genset starts
according to the Start sequence. When the genset loading
voltage and frequency are above the Minimum healthy
thresholds, the Warm-up delay timer starts. At the end of
the Warm-up delay, the Load transfer delay starts and the
genset latches. The running hours stop increasing when a
Stop command is received.
Stop the engine
Shutdown Alarm
Warning Alarm
Notification
Press the Stop/Config button to stop the running
engine.
Press the Stop/Config
button twice to stop the
engine immediately.
When the Stop/Config
button is pressed, the
controller opens the genset contactor, and the Engine
cooling time starts. At the end of the Engine cooling time,
the controller initiates the Stop sequence by giving the
Stop command.
If the Stop/Config
button is pressed during Engine
cooling time, the controller skips the Cooling time and
sends the Stop command immediately.
Test mode
In manual mode (while the genset is OFF) if the Mode selection
button is long pressed, the controller goes in Test mode. Test
mode is almost the same as manual mode, but in Test mode the genset contactor will not get latched. If the Genset contactor
latching button is pressed, only the genset contactor gets latched. Once the genset starts in Test mode, the Test mode timer
starts. After the Stop/Config button is pressed or the timer has run out, the controller sends a Stop command and the genset
stops according to the Stop sequence.