Parameter Scale Factor
Unit/
Interpretation
Bits/Sign
91
DG status
GCU Mode
Config
Run
16/16
Mains healthy/Unhealthy --
True (1)
False (0)
15/16
DG operation mode --
Scheduler
Cyclic
Auto
Manual
14-12/16
Load on DG
True (1)
False (0)
11/16
Load on Mains --
True (1)
False (0)
10/16
Current DG status --
Running
Stopped
9/16
DG stopped normally --
True (1)
False (0)
8/16
DG stopped with fault
True (1)
False (0)
7/16
DG fail to start --
True (1)
False (0)
6/16
Gen available
True (1)
False (0)
5/16
Common shut down --
True (1)
False (0)
4/16
Common electric trip --
True (1)
False (0)
3/16
Common warning --
True (1)
False (0)
2/16
Common notification --
True (1)
False (0)
1/16
92 Current time stamp --
Min
Sec
Hexadecimal
93 Current time stamp
Week day
Hour
Hexadecimal
94 Current time stamp
Month
Day
Hexadecimal
95 Current time stamp Year Unsigned
Table 12.1 Example of Time stamp settings
Register address Time Hexadecimal Decimal
92
Min
0x1215
Min = 0x12 18
Sec Sec = 0x15 21
93
Week day
0x0414
Week day = 0x04 4
Hour Hour = 0x0E 14