Communication structure, page 26
Register offset Value Scale factor Unit Bits/Sign
73
Alarm 10
Gen L1 phase low volt -
E-0001/0001
W-0010/0010
S-0011/0011
13/16-16/16
Gen L1 phase high volt -
E-0001/0001
W-0010/0010
S-0011/0011
9/16-12/16
Gen L2 phase low volt -
E-0001/0001
W-0010/0010
S-0011/0011
5/16-8/16
Gen L2 phase high volt -
E-0001/0001
W-0010/0010
S-0011/0011
1/16-4/16
74
Alarm 11
Gen L3 phase low volt -
E-0001/0001
W-0010/0010
S-0011/0011
13/16-16/16
Gen L3 phase high volt -
E-0001/0001
W-0010/0010
S-0011/0011
9/16-12/16
DG phase rotation -
E-0001/0001
N-0101/0101
W-0010/0010
E-0100/0100
S-0011/0011
5/16-8/16
Mains phase rotation -
E-0001/0001
N-0101/0101
1/16-4/16
75
Alarm 12
Fuel level open circuit -
E-0001/0001
N-0101/0101
W-0010/0010
E-0100/0100
S-0011/0011
13/16-16/16
V belt broken -
E-0001/0001
N-0101/0101
W-0010/0010
E-0100/0100
S-0011/0011
9/16-12/16
Extended overload trip -
E-0001/0001
S-0011/0011
5/16-8/16
High oil pressure detected -
E-0001/0001
W-0010/0010
1/16-4/16