Register offset Value Scale factor Unit Bits/Sign
77
DG status
Controller mode -
Config (1)
Run (0)
16/16
Mains healthy/unhealthy -
True (1)
False (0)
15/16
DG operation mode -
Scheduler-110
Cyclic-111
Auto-101
Manual-100
14-12/16
Load on Mains -
True (1)
False (0)
11/16
Load on DG -
True (1)
False (0)
10/16
Current DG status -
Running
Stopped
9/16
DG stopped normally -
True (1)
False (0)
8/16
DG stopped with fault -
True (1)
False (0)
7/16
DG fail to start -
True (1)
False (0)
6/16
Gen available -
True (1)
False (0)
5/16
Common shutdown -
True (1)
False (0)
4/16
Common electric trip -
True (1)
False (0)
3/16
Common warning -
True (1)
False (0)
2/16
Common notification -
True (1)
False (0)
1/16
Communication structure, page 28
Register offset
Value Scale factor Unit Bits/Sign
78-81 Current time stamp
Structure of broadcast message
Byte no.
Byte contents
0 Page ID
1 Data at offset 0 - high byte
2 Data at offset 0 - low byte
3 Data at offset 1 - high byte
4 Data at offset 1 - low byte
5 Data at offset 2 - high byte
6 Data at offset 2 - low byte
7 Reserved
USER MANUAL 4189341227A UK Page 82 of 86