EasyManua.ls Logo

Dell EMC VMAX 250F - Customer Input Power Cabling for VMAX 250 F

Dell EMC VMAX 250F
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VMAX 250F customer AC power feed cabling
When connecting customer input power to a VMAX 250F, the EMC-supplied 15ft
(4.57m) extension cords must be used and approximately 24in (61cm) of slack must
be left directly under the bay floor egress.
Note
For power zone-A, use the extension cord with gray sleeves at the ends.
Figure 44 Customer input power cabling for VMAX 250F
Rear view
Example shown:
2 V-Bricks
PDPs
Customer’s
PDU 2
Power feed 2
Customer’s
PDU 1
Circuit breakers - Numbers
27
28
29
30
...
Circuit breakers - Numbers
27
28
29
30
...
Power feed 1
1010
A
B
1010
A
B
ON
I
OFF
O
ON
I
OFF
O
ON
I
OFF
O
ON
I
OFF
O
ON
I
OFF
O
ON
I
OFF
O
EMC 15ft (4.57m) Extension Cord
with 24in (61cm) slack under floor egress
Customer
power feed
Customer
power feed
PDUs
40U rack
PDP
PDU
Power zone A
(right, gray)
Power zone B
(left, black)
(Power zone B)
(Power zone B)
(Power zone A)
(Power zone A)
Data center sub-floor
Data center floor
Best Practices for AC Power Connections
Procedure A, Task 2: EMC Customer Engineer (VMAX 250F) 123

Table of Contents

Related product manuals