Dimensions for array layouts
Placing arrays in the data center or computer room involves understanding
dimensions, planning for cutouts, and ensuring clearance for power and host cables.
l
On nonraised floors, cables are routed overhead. An overhead routing bracket is
provided to allow easier access of overhead cables into the bay
l
On raised floors, cables are routed across the subfloor beneath the tiles.
l
Ensure there is a service area of 42 in (106 cm) for the front and 30 in (76 cm) for
the rear of each system bay.
The following figure shows the layout dimensions:
Figure 7 Layout Dimensions, VMAX 450F, VMAX 850F, VMAX 950F
Front
Rear
47 in.
(119 cm)
Includes
front and
rear doors
.25 in. (.64 cm) gap
between bays
24.02 in.
(61.01 cm)
24 in.
(61 cm)
Position VMAX 450F, VMAX 850F, VMAX 950F Bays
54 Site Planning Guide VMAX 250F, VMAX 450F, VMAX 850F, VMAX 950F with HYPERMAX OS