Power distribution equipment for third-party rack, VMAX 250F
Refer to the tables below for outlet connectivity requirements based on the quantity
of V-bricks in the system.
Table 27 Power Distribution Equipment C13 Outlet Connections required for 1 V-Brick
Component
Number of C13 outlets required
TotalsZone A Zone B
25 drive 2U DAE
(DAE 2)
1 1 2
25 drive 2U DAE
(DAE 1)
1 1 2
4U Engine (1)
+ 2U SPS
(SPS 3A and 3B)
1 1 2
Total C13 outlets: 6
Table 28 Power Distribution Equipment C13 Outlet Connections required for 2 V-Bricks
Component
Number of C13 outlets required
Totals
Zone A C13
outlets
Zone B C13 outlets
25 drive 2U DAE
(DAE 4)
1 1 2
25 drive 2U DAE
(DAE 3)
1 1 2
4U Engine (2)
+ 2U SPS
(SPS 2A and 2B)
1 1 2
25 drive 2U DAE
(DAE 2)
1 1 2
25 drive 2U DAE
(DAE 1)
1 1 2
4U Engine (1)
+ 2U SPS
(SPS 3A and 3B)
1 1 2
Total C13 outlets: 12
Third Party Racking Option for VMAX 250F