25DAE power requirements
Table 26 25 drive DAE power requirements
Requirement Description
AC line voltage 100 to 240V AC ± 10%, single-phase, 47 to 63
Hz
AC line current (operating maximum)
4.73 A max at 100V AC
2.50 A max at 200V AC
Power consumption (operating maximum)
473 VA (442 W) max, at 100V AC
500 VA (435 W) max, at 200V AC
Heat dissipation (operating maximum)
1.59 x 10
6
J/hr. (1,508 Btu/hr.) max @ 100V
AC
1.80 x 10
6
J/hr, (1706 Btu/hr) max @ 200Vac
In-rush current 30 Apk "cold" per line cord at any line voltage
Startup surge current 40 Apk "hot" per line cord, at any line voltage
AC protection 15 A fuse on each power supply, both phases
AC inlet type IEC320-C14 appliance coupler, per power
zone
l
Ratings assume a fully loaded DAE that includes 2 power supplies and 25 worst case disk
drives operating in an ambient environment above 35°C. For specific product
configuration power numbers, refer to the EMC power calculator, https://
powercalculator.emc.com.
l
Product power may vary depending on each product configuration and ambient operating
temperature.
l
All power figures shown represent max normal operating numbers with the chassis running
in a normal ambient temperature environment. The chassis power numbers given may
increase 5% when running in a higher ambient temperature environment.
Third Party Racking Option for VMAX 250F
Component power requirements, VMAX 250F 93