Loading...
Customer-to-system wiring (three-phase, North American (Delta))
The following figures provide cable descriptions for three-phase North American
(Delta) power transmission.
Figure 28 Three-phase, North American, Delta: EF-PCBL3DHR (VMAX 450F, VMAX 850F), ET-
PCBL3DHR (VMAX 950F), ES-PCBL3DHR (VMAX 250F)
P1 P2
CS8364 Russellstoll 9P54U2
CS8364
9P54U2
Color
BLK
WHT
RED
GRN
From
P1-X
P1-Y
P1-Z
P1-G
To
P2-X
P2-Y
P2-Z
P2-G
Signal
L1
L2
L3
GND
X
Y
Z
X
Y
Z
Power cord wiring diagram
Figure 29 Three-phase, North American, Delta: EF-PCBL3DHH (VMAX 450F, VMAX 850F), ET-
PCBL3DHH (VMAX 950F), ES-PCBL3DHH (VMAX 250F)
P1 P2
CS8364 CS8365
CS8364 CS8365
Color
BLK
WHT
RED
GRN
From
P1-X
P1-Y
P1-Z
P1-G
To
P2-X
P2-Y
P2-Z
P2-G
Signal
L1
L2
L3
GND
Y
Z
ZX
X
Y
Power cabling, cords and connectors
84 Site Planning Guide VMAX 250F, VMAX 450F, VMAX 850F, VMAX 950F with HYPERMAX OS