footprint. Once you have positioned, leveled, and stabilized the cabinet, the four
leveling feet determine the final load-bearing points on your site floor.
CL3627
Front
Rear
Front
Rear
Outer surface
of rear door
Outer surface
of rear door
18.830
20.700
28.240
(based on swivel
position of caster wheel)
17.102 minimum
(based on swivel
position of caster wheel)
20.580 maximum
Top view
Rear view Rear view
Note: Some items in the views are removed for clarity.
Right
side view
Dimension 3.620 to center of
caster wheel from this surface
(see detail A)
Dimension 3.620
to center of caster
wheel from this surface
3.620
27.370
minimum
(based on
swivel position
of caster wheel)
29.120
maximum
(based on
swivel position
of caster wheel)
1.750
Swivel diameter
reference (see
detail B)
Detail A
(right front
corner)
1.750
Caster swivel
diameter
Detail B
20.650
35.390
Bottom view
Leveling feet
Leveling feet
Floor tile
cutout
All measurements are in inches.
The customer is ultimately responsible for ensuring that the data center floor on which
the system is to be configured is capable of supporting the system weight, whether
the system is configured directly on the data center floor, or on a raised floor
supported by the data center floor. Failure to comply with these floor-loading
requirements could result in severe damage to the system, the raised floor, subfloor,
site floor and the surrounding infrastructure. Notwithstanding anything to the
contrary in any agreement between the manufacturer and customer, the manufacturer
fully disclaims any and all liability for any damage or injury resulting from customer's
failure to ensure that the raised floor, subfloor and/or site floor are capable of
supporting the system weight as specified in this guide. The customer assumes all risk
and liability associated with such failure.
Position VMAX 250F Bay
46 Site Planning Guide VMAX 250F, VMAX 450F, VMAX 850F, VMAX 950F with HYPERMAX OS