14 Installing the Hardware
  NOTE: Please take precautions against over-tightening the screws or nuts on this 
device.
Installing a DC PEM
Step Task
1 Turn the remote power source (the circuit breaker panel) to the OFF 
position.
2 Turn the over current protector (located on the PEM front panel) to the 
OFF position.
3 Loosen the PEM safety cover retaining screw and remove the cover.
4 Slide the PEM into power slot 0 or 1.
  CAUTION: Fill all power supply slots with power supplies or 
filler blanks before tightening the power supply screws. Doing 
this ensures that each power supply is aligned correctly. 
Attempting to tighten screws without all power supply slots 
filled will cause misalignment with screw holes, which might 
damage the chassis permanently. If you are only installing one 
PEM, replace the empty slot with two blank panels. (CC-
E300-BLNK-PWR.)
5 Tighten the two locking screws on each module with a #2 Phillips 
screwdriver to secure the PEM in place. As a best practise, insert all 
screws before tightening each one.
6 Remove the outer nut and washer from each of the remaining studs.
7 Connect the -48 VDC and Return cables from each PEM to the remote 
power sources.
a
Verify that the remote power source is in the OFF position.
b
Locate the appropriate studs on the PEM front panel. The two top 
studs are the return (+) connection. The cable attached to these studs 
is typically red. The two bottom studs on the PEM are the -48 VDC (-
) connection. The cable attached to these studs is typically black. 
Power cables must be terminated only with a UL-listed 2-hole lug to 
accommodate 1/4-inch studs with 3/4-inch spacing.
c
Apply a coat of anti-oxidant paste to the connector studs.
d
Replace the washers and nuts on the studs.
e
Route the terminated cables out toward the rack rail.
f
Secure the nuts with a nut driver or torque wrench (not to exceed 4 
ft/lbs).