32 Installing the Hardware
E600i ExaScale Environmental Parameters
E600i ExaScale AC Power Supply Unit Requirements
Maximum for fully loaded chassis 120 VAC powered: 4705W (16,065
BTU/hour)
200/240 VAC powered: 4250W (14,500
BTU/hour)
DC powered: 2800W (9600 BTU/hour)
Parameter Specifications
Operating
Temperature 32° to 104°F (0° to 40°C)
Maximum altitude No performance degradation to 10,000 feet (3,048 meters)
Relative humidity 5 to 85 percent, non-condensing
Non-operating
Temperature -40° to 158°F (-40° to 70°C)
Maximum Altitude 15,000 feet (4,572 meters)
Relative Humidity 5 to 95 percent, non-condensing
Parameter Specifications
Nominal input voltage 120 - 240 VAC 50/60 Hz
Maximum AC Power Supply Input 16 A @ 100 VAC per module
12 A @ 200 VAC per module
Maximum Thermal Output (3,172 W)
Maximum Thermal Output (2,906 W)
10,822 BTU/hour at 100/120 VAC
9,914 BTU/hour at 200/240 VAC
Maximum AC Supply Input Current
(based on 2500 W output for 100/120V
and 200/240V lines.)
11.6 A @ 100 VAC
9.7 A @ 120 VAC
8.0 A @ 200 VAC
6.7 A @ 240 VAC
Maximum System Power Input 3.5 KVA @ 100/120 VAC
3.2 KVA @ 220/240 VAC
Parameter Specifications