AS Series Operation Manual 
5-4 
5.1.3  Relation Between the PLC Action and the Device Type 
Device type 
PLC action 
Non-latched area  Latched area 
Device Y  Other devices  File register  Other devices 
Power: OFF→ON 
Cleared  Cleared  Retained  Retained 
Restore to defaults 
Cleared  Cleared  Cleared  Cleared 
STOP 
↓ 
RUN*
1
 
This clears the   
non-latched area 
state. 
Cleared  Cleared  Retained  Retained 
This retains the 
non-latched area 
state. 
Retained  Retained  Retained  Retained 
RUN 
↓ 
STOP*
1
 
This clears the   
device Y state. 
Cleared  Retained  Retained  Retained 
This retains the 
device Y state. 
Retained  Retained  Retained  Retained 
SM204 is ON.This clears all 
non-latched areas.*
2
 
Cleared  Cleared  Retained  Retained 
SM205 is ON.This clears all 
latched areas.*
2
 
Retained  Retained  Retained  Cleared 
*1: For state setups, see HWCONFIG in ISPSoft. The PLC STOP->RUN default is “clear the non-latched area 
state”. The PLC RUN->STOP default is “clear the state of device Y”.   
*2: The timing for clearing the SM is when SM turns from OFF to ON. After PLC completes clearing, the 
system turns SM from ON to OFF.